All-steel ventilated floor

All-steel ventilated floor


The all-steel ventilated floor uses high-quality cold-rolled steel plates, stamped and welded into shape, filled with foamed cement. Customized ventilation louvers are cut into the surface, allowing for ventilation rates ranging from 20% to 55% in various specifications. The overall structure is robust and load-bearing, fire-resistant to Class A, and the surface is wear-resistant and corrosion-resistant, compatible with various anti-static surface layers such as HPL and ceramic.

WhatsApp: +8615515788212

Email: sales@aobeitefloors.com

Product detail

All-steel ventilated floor

Product Description

The all-steel ventilated floor uses high-quality cold-rolled steel plates, stamped and welded into shape, filled with foamed cement. Customized ventilation louvers are cut into the surface, allowing for ventilation rates ranging from 20% to 55% in various specifications. The overall structure is robust and load-bearing, fire-resistant to Class A, and the surface is wear-resistant and corrosion-resistant, compatible with various anti-static surface layers such as HPL and ceramic.

The floor is installed in a raised structure with supporting beams. This raised space not only accommodates power cables in the server room but also facilitates airflow under the racks and air circulation for heat dissipation, while simultaneously dissipating static electricity to prevent damage to precision equipment. It is easy to install and disassemble, highly interchangeable, and can be seamlessly integrated with ordinary all-steel anti-static floors for flexible placement directly beneath server racks.

Application Scenarios

1. Big Data Server Rooms and Server Rooms: Utilizes bottom-mounted airflow for optimal cooling and heat dissipation;

2. IDC Data Centers and Cloud Computing Rooms: Works with precision air conditioning to improve overall temperature control and heat dissipation;

3. Telecommunications Rooms and Broadcast Control Rooms: Provides ventilation, cabling organization, and anti-static properties;

4. Power Distribution Rooms and Precision Instrument Laboratories: Ensures heat dissipation and moisture protection, guaranteeing constant temperature operation of equipment.

Main Specifications
Standard size 600×600mm
Floor thickness 40mm (standard) / 45mm (heavy-duty)
Elevation height 100–300mm (customizable)
Ventilation rate 20%/30%/45%/55% (optional)
System resistance 1×10⁶~1×10⁹Ω
electrostatic attenuation ≤2s (1000V→100V)
Uniformly distributed load ≥12500N/m²
Concentrated load ≥5560N (Standard) / ≥9000N (Heavy-duty)
Deflection ≤2.0mm
Mohs hardness ≥6 levels
Wear resistance rotation speed ≥2000 RPM
Fire resistance rating Class A (non-flammable)
steel plate thickness 0.8–1.2mm
Single piece weight Approximately 27–32 kg